Specifications

MCSBMSGATEWAYStartupGuide Revision4.0
MicroControlSystems5580EnterprisePkwy,FortMyers,FL33905USAWeb:www.mcscontrols.com
Tel:(239)6940089Fax:(239)6940031
38
Appendix A.3. LED Diagnostics for Lonworks Communications between the MCSBMSGATEWAYand
device
Note:PleaseseethediagrambelowforLEDLocations
A.2.1LonWorksProtoCessorLED’s
––

Light Description
PWR
ThisisthepowerlightandshouldshowsteadygreenatalltimeswhentheMCSBMSGATEWAY
MCSBMSGATEWAYispowered.
SYSERR
(LED1)
TheSYSERRLEDwillflashonceonpowerupandflashonce15secondsafterpowerup.Asteadyred
lightwillindicatethereisasystemerrorontheMCSBMSGATEWAY.Ifthisoccurs,immediately
reporttherelated“systemerror”shownintheerrorscreenoftheRUI
interfacetoMicroControl
Systemsforevaluation.
COMM
ERR
(LED2)
TheCOMMERRLEDwillflashonceonpowerupandflashonce15secondsafterpowerup.Asteady
redlightwillindicateacommunicationerrorhasoccurred.Toestablishthecauseoftheerror,goto
theerrorscreenoftheRUIinterface.
Config
ERR
(LED3)
TheConfigERRLEDwillflashonceonpowerupandflashonce15secondsafterpowerup.Asteady
amberlightwillindicateaconfigurationerrorexistsintheactiveconfiguration.SeetheErrorScreen
intheRemoteUserInterfaceforadescriptionoftheconfigurationerror.
Node
Offline
(LED4)
TheNodeOfflineLEDwillflashonceonpowerupandflashonce15secondsafterpowerup.Ifthe
NodeOfflineLEDstaysonsolid,aNodeOfflineconditionhasoccurred.
RUN
(PIO)
TheRUNLEDwillstartflashing20secondsafterpowerindicatingnormaloperation.TheMCSBMS
GATEWAYwillbeabletoaccessRUINEToncethisLEDstartsflashing.
PICRUN
(LED5)
ThePICRUNLEDwillflashindicatingnormaloperation.
LONLED
LONTX
RUN
SYSERR
COMERR
ConfigERR
Nodeoffline
LONRX
PWR
PICRUN
PICERR
UNUSED
UNUSED
Figure17 LonWorksProtoCessorLED’s