AppendixA. TroubleshootingTips
AppendixA.1. ConnectingAPCtotheMCS‐BMS‐GATEWAY
Confirmthatthenetworkcablingiscorrect
Confirmthatthecomputernetworkcardisoperationalandcorrectlyconfigured
Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and that it is
configuredtoruntheTCP/IPprotocol
CheckthattheIPnetmask
ofthePCmatchestheMCS‐BMS‐GATEWAY.TheDefaultIPAddressoftheMCS‐
BMS‐GATEWAYis192.168.10.85,SubnetMaskis255.255.255.0,DefaultGatewayis192.168.10.1.
GotoStart>Run
Typein“ipconfig”
Theaccountsettingsshouldbedisplayed
Ensure that the IP address
is 192.168.10.xxx, the Subnet mask is 255.255.255.0 and the Default
Gatewayis192.168.10.1
EnsurethatthePCandMCS‐BMS‐GATEWAYareonthesameIPNetwork,orassignaStaticIPAddressto
thePConthe192.168.10.network
IfUsingWindowsXP,ensurethatthefirewallis
disabled
EnsurethatallotherEthernetcardsactiveonthePC,especiallywirelessadaptersaredisabled
AppendixA.2. NocommunicationbetweentheMCS‐MagnumandtheMCS‐BMS‐GATEWAY
Confirmthatthenetworkcablingiscorrect
Check that the IP address, subnetmask, and the default gateway of the MCS‐Magnum match what the
labelontheMCS‐BMS‐GATEWAYsaysitshouldbesetto.
Check the LED’s on the Ethernet port. The yellow LED should be
solid yellow the green LED should
continuouslyflash.
EthernetPort
GreenLED
YellowLED