Operational Modes
All modes operate the overhead fan and/or a heating or cooling cycle based on the current
heating or cooling set-point, relative to the inside temperature.
Fans and Fan Only Mode
This mode lets the fan to operate based on the chosen (8) Fan Speed.
This will circulate the air without operating any heating or cooling cycles.
Cool Only Mode
This mode only runs a cool cycle to maintain the cooling set-point in the
space. Set the (7) Operational Mode button to Cool Only and the desired (8) Fan
Speed, where behavior will then be based on Table 5. A time delay of
approximately three minutes occurs before a cooling cycle begins. This allows
pressure to equalize in the system to prevent compressor damage.
Environment (°F)
Cycle Operation
Auto Fan Operation
Inside (Setpoint + 1°)
None
Off
Inside 2° Above Setpoint
Cooling Cycle Begins
On Low
Inside 3°- 5°Above Setpoint
Cooling Cycle Continues
On Medium
Inside 6° Or More Above Setpoint
Cooling Cycle Continues
On High
Inside Returns Setpoint
Cooling Cycle Terminates
Runs 30 More Seconds, Off
Table 5 - Cool Only Mode Operation
Note: Table 5 operation may be different based on the Gap settings. See section Temperature Gap
(Hysteresis) for details.
Furnace Only or Aqua Only Mode
This mode only runs an auxiliary heating cycle to maintain the heating set-
point in the space. Set the (7) Operational Mode button to Furnace Only or Aqua
Only and the desired overhead (8) Fan Speed, where behavior will then be based
on Table 6. Furnace fan speed is not configurable from the thermostat. See section
Furnace/Aqua Icons for details on the auxiliary heating icon.
Environment (°F)
Cycle Operation
Auto Fan Operation
Inside (Setpoint - 1°)
None
Off
Inside 2° Below Setpoint
Auxiliary Heat Cycle Begins
On Low
Inside 3°- 5° Below Setpoint
Auxiliary Heat Cycle Continues
On Medium
Inside 6° Or More Below Setpoint
Auxiliary Heat Cycle Continues
On High
Inside Returns Setpoint
Auxiliary Heat Cycle Terminates
Runs 30 More Seconds, Off
Table 6 - Furnace Only Mode Operation
Note: Table 6 operation may be different based on the Gap settings. See section Temperature Gap
(Hysteresis) for details.
Fan Only Mode
Fan Speed
Cool Only Mode
Aqua Only Mode
Furnace Only Mode