EasyTouch RV 351 Manual

13
©2022 Micro-Air Corp June 15, 2022, revision 1.5
Installation Troubleshooting
The most common problem is not knowing the thermostat operation. If the system is running a
heating or cooling cycle, the set point will turn red for heating and blue for cooling. When the
thermostat turns white, the heat pump, heat strip and furnace should all be off. The fan may continue to
run for a while after the cycle completes. If a fan is left in a manual mode, it will not shut off.
WIFI Troubleshooting
No WIFI Icon
SSID (Network name) and password are both case sensitive.
Be sure you are connecting to a 2.4 GHz network and not a 5GHz or 6GHz network.
Set the security to WPA2 and TKIP+AES if you are having trouble.
The thermostat has a limit of 31 characters for the SSID and 50 for the password.
The number of devices limit for the network is not full.
The WIFI source is not out of range or metal partitions blocking the signal
Reset the router to renew the DHCP lease.
If you are in a metal enclosure, try moving the router or thermostat a few inches (even if
temporary) and trying again.
If using MAC filtering, add the thermostat to the allowed devices list.
Be sure the router SSID is not set for “Hidden”.
Red WIFI Icon
The router must have an internet connection
Server may be down, check back at a later time
Be sure there is no firewall in the router blocking the incoming messages (port 443, HTTPS).
Fault Messages
Freeze Fault: Temperature of inside coil has dropped below 30°F (-1°C). The compressor will
turn off and the fan will run until the inside coil sensor temperature reaches 54°F (12°C). The
compressor will then run again if required. This fault can mean the air flow is restricted, filter is
clogged, outside coils are dirty, refrigerant is low, humidity is very high, or the sensor is bad if
becomes a recurring problem.