COOKSON OWNER'S MANUAL VERSION 5 WIRELESS SELF MONITORING SENSING EDGE SYSTEM PATENT NO. 6,225,768 9046.
SPECIFICATIONS COMPATIBLE WITH THE FOLLOWING OPERATORS: - MGJ / H / GH / FDO-A / FDO-B / FDO-A10 NOT COMPATIBLE WITH OTHER (RF) RADIO FREQUENCY DEVICES TRANSMITTER ENCLOSURE MATL:..............POLYCARBONATE ENCLOSURE COLOR:...........BLACK ENCLOSURE RATING:..........NEMA 4 OPERATING TEMP:...............-25° F TO 120° F OPERATING FREQUENCY:..315 Mhz MAX OPER DISTANCE:.........50 FT POWER:..................................9 VOLT LITHIUM BATTERY EXPECTED BATTERY LIFE:.12 MOS-NORMAL USAGE ANTENNA TYPE:.........
THEORY OF OPERATION GENERAL DESCRIPTION: The Phantom Edge is a self monitoring wireless (RF) sensing edge system. A special communication protocol between the transmitter and receiver allow for additional signals (other than edge activation) to be sent, such as battery condition and periodic communication checks. If the unit detects a fault it will convert the operator to supervised mode (i.e. constant pressure contact on operator close control) indicating that maintenance is required.
5) Be sure that the battery strap is connected and insert the lithium ion 9 Volt battery into the cover of the unit, and replace the cover. The green LED light should light indicating that the unit is functioning properly. 6) Remove cover and disconnect battery until receiver is installed. RECEIVER INSTALLATION: NOTE: THE OPERATOR REQUIRES AN EXTRA, DEDICATED AUXILIARY CLOSE LIMIT SWITCH.
START UP / TESTING PROCEDURES RECEIVER (ON OPERATOR) INITIAL POWER UP: NOTE: MAKE SURE TRANSMITTER BATTERY IS DISCONNECTED OR THE TRANSMITTER IS IN MOTIONLESS "SLEEP" MODE BEFORE POWERING THE RECEIVER. 1) The unit will be in "Supervised Mode": Constant pressure required on door CLOSE control - 2 LED's under the label will be lit. 2) Hold closed door control: - (D3) "Transmitter Awake" (GREEN) LED will lite when door is in motion. - (D8) "Signal Acquired" (GREEN) LED will lite when edge is pressed.
3) Open door several feet - Verify that unit is still in "Supervised Mode". Constant pressure required on door CLOSE control. 4) Reconnect sensing edge to Transmitter. 5) Close door completely: Unit will switch to "Normal Mode" (within 3 sec). - (D6) "Normal Mode" (GRN) LED will light. Door now requires momentary contact for CLOSE control. TROUBLESHOOTING 1) Verify address selection dip switches (1 thru 4) are set the same on the Transmitter and Receiver.
LABEL AND MANUAL INFORMATION 1) Labeling Requirement In accordance with the Section 15.19 of FCC Rules, a permanently attached label shall be affixed to every product in a conspicuous location with the following statement: "This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 1) This device may not cause harmful interference, and 2) this device must accept any interference received, including interference that may cause undesired operation.
APPENDIX INDEX DESCRIPTION PAGE LIFTMASTER WIRING DIAGRAM - LIFTMASTER GH/H A-1 WIRING DIAGRAM - LIFTMASTER MGJ A-2 WIRING DIAGRAM - LIFTMASTER - MGJ 3 PHASE A-3 WIRING DIAGRAM - FDO-A / FDO-B A-4 MICANAN WIRING DIAGRAM - PRO GH/H A-5 COOKSON WIRING DIAGRAM - FDO-A10 A-6 8
LIFTMASTER GH/H WIRING DIAGRAM RED WIRE NUT FROM TRANSFORMER WIRE NUT (FIELD INSTALLED) (REMOVE) THIS IS AN ADDITIONAL SWITCH INSTALLED FOR USE EXCLUSIVELY BY THE PHANTOM EDGE 1 2 4 3 5 7 L1 10 L2 L3 ORANGE BROWN GREEN BLUE YELLOW AUX CLOSE LIMIT SW RED N.C. N.O.
LIFTMASTER MGJ - SINGLE PHASE RED WIRING DIAGRAM WIRE NUT (FIELD INSTALLED) THIS IS AN ADDITIONAL SWITCH INSTALLED FOR USE EXCLUSIVELY BY THE PHANTOM EDGE 2 3 4 5 7 11 10 12 BLUE 1 (REMOVE) BROWN ORANGE BLACK PURPLE PHANTOM EDGE RECEIVER A-2 YELLOW BLACK GREEN RED PURPLE COM PURPLE PURPLE BLUE RED BROWN N.O. NOT USED GREEN N.C.
LIFTMASTER MGJ - 3 PHASE WIRING DIAGRAM TRANSFORMER (FIELD INSTALLED) WIRE NUT RED BROWN WIRE NUT RED (REMOVE) THIS IS AN ADDITIONAL SWITCH INSTALLED FOR USE EXCLUSIVELY BY THE PHANTOM EDGE 1 2 4 3 5 7 10 ORANGE BLACK BLUE GREEN AUX CLOSE LIMIT SW YELLOW N.C. N.O.
FDO-A/FDO-B OPERATOR WIRING DIAGRAM THIS IS AN ADDITIONAL SWITCH INSTALLED FOR USE EXCLUSIVELY BY THE PHANTOM EDGE AUX CLOSE LIMIT SW N.C. N.O.
WHITE MICANAN GH/H WIRING DIAGRAM RED (REMOVE) 1 2 4 3 5 6 7 8 9 THIS IS AN ADDITIONAL SWITCH INSTALLED FOR USE EXCLUSIVELY BY THE PHANTOM EDGE ORANGE YELLOW GREEN AUX CLOSE LIMIT SW BLUE N.C. N.O.
FDO-A10 WIRING DIAGRAM WALL MOUNTED CONTROL PANEL WIRE NUT (FIELD INSTALLED) 1 THIS IS AN ADDITIONAL SWITCH INSTALLED FOR USE EXCLUSIVELY BY THE PHANTOM EDGE 2 3 4 5 (REMOVE) YELLOW FROM TERMINAL 14 ON CLOSE CONTACTOR 10 6 11 A2 A1 L1 L2 GREEN ORANGE BLACK BLUE BROWN RED PURPLE N.C. INSIDE MOTOR CONTROL PANEL PHANTOM EDGE RECEIVER A-6 GREEN BLACK RED BROWN PURPLE PURPLE COM BLUE N.O.