Watlow Series C 16 • Troubleshooting
Indication Probable Cause(s) Corrective Action
Troubleshooting RTD inputs
Temperature reading is in-
correct, showing a sensor er-
ror, [Er;In] , or LOAD LED
is switching at the wrong
temperature.
• Calibration offset incorrect (tactile
models only).
Check calibration offset
• Settings for degree C or F is incorrect. Check model part number for degree C or F.
If model has Increment/Decrement keys then
C/F setting is adjustable.
• Sensor or controller may be bad. Sen-
sor connections may be bad.
• Place a 110 ohm resistor across the sensor
input terminals. The display should indicate
25°C (77°F). If it does, the controller is OK.
Sensor or connections may be bad.
For controllers without the ability to view
process temperature:
- Decrease set point below ambient tempera-
ture, LOAD LED should be off for heating
controllers and on for cooling controllers.
- Increase set point above ambient tempera-
ture. LOAD LED should be on for heating
controllers and off for cooling controllers.
Ambient temperature in the control
cabinet is over 70°C (158°F).
• Measure temperature in cabinet to ensure
it is below 70°C (158°F). Vent cabinet or add
fans if necessary.
• Sensor connections may be bad. Ex-
cessive lead wire resistance.
• Check sensor connections. Measure lead
wire resistance. There will be a 2.6°C (4.7°F)
error for every ohm of lead wire resistance.
Troubleshooting controller outputs
Controller output signal is
not on when it should be.
Load LED is not on.
Temperature reading is incorrect on
display of indicating controls or limit.
See input troubleshooting.
• See input troubleshooting.
Set point is not set correctly.
Verify set point setting.
Controller output signal is
not on when it should be.
Load LED is on.
• Output wiring is incorrect. Verify wiring. Relay outputs act as a
switch, they do not source power.
For DC output controls, voltage should be
about 20VDC with no load. Greater than 5
volts with load of 500 Ω or greater.
Control output signal is on
when it should not be on.
Load LED is on.
Temperature reading is incorrect on
display of indicating controls or limit.
see input troubleshooting.
• See input troubleshooting.
• Set point is not set correctly. Verify set point setting.
• Control output is defective. • Repair or replace controller.
Load is on when it should
not be on. Load LED is off.
• Power switching device (SSR, HG
relay, mechanical relay) is shorted. Con-
troller outputs shorted.
• Remove wires from output of control to in-
put of power switching device. If load is still
on, replace power switching device. If load
turns off, replace controller or sensor. See in-
put troubleshooting.
• Output wiring is incorrect. Verify wiring.