User`s manual

Watlow Series C 15 • Troubleshooting
Troubleshooting
Indication Probable Cause(s) Corrective Action
On indicating controls, the
display is not illuminated.
• Power supply switch off.
Turn switch on.
• Fuse blown.
• Replace fuse (check cause of failure).
• Breaker tripped.
• Reset breaker (check cause of failure).
• Safety interlock door switch activated.
• Close door.
• Separate system limit control latched.
• Reset limit controller.
Wiring incorrect or open.
• Check wiring.
• Power supply voltage incorrect.
Verify input power.
• Defective controller.
• Repair or replace controller.
Troubleshooting thermocouple inputs
Temperature reading is
incorrect, showing a sen-
sor error, [Er;In] , or LOAD
LED is switching at the
wrong temperature.
Calibration offset is incorrect (tactile
models only).
Check calibration offset.
Settings for degree C or F is incorrect. Check model part number for degree C or F.
If model has Increment/Decrement keys then
C/F setting is adjustable.
Sensor or controller may be bad.
Sensor connections may be bad.
• Place a jumper wire across the thermo-
couple input terminals. The display should
indicate ambient temperature. If it does, the
controller is OK.
For controllers without the ability to view
process temperature:
- Decrease set point below ambient tempera-
ture, LOAD LED should be off for heating
controllers and on for cooling controllers.
- Increase set point above ambient tempera-
ture. LOAD LED should be on for heating
controllers and off for cooling controllers.
Ambient temperature in the control
cabinet is over 70°C.
• Measure temperature in cabinet to ensure
it is below 70C. Vent cabinet or add fans if
necessary.
Ground loop problem. Can occur
when using a switched DC output and
a grounded thermocouple.
• Remove power from the system. Use an
ohm meter to measure resistance between
output DC- and the thermocouple sheath. If
there is continuity, replace sensor with an
ungrounded thermocouple.
Temperature reading is de-
creasing, but actual process
is increasing.
Thermocouple polarity is reversed. In
the US, red wire insulation denotes the
negative wire.
• Check thermocouple connections. All con-
nections, including extension wire must
maintain the correct polarity. Correct polarity
problems.
Temperature reading is
reading low and not increas-
ing while actual process
temperature is increasing.
• Sensor is bad. Thermocouple is short-
ed.
• Check thermocouple connections. Check
thermocouple wire insulation to make sure
it is not damaged, causing the wires to short
(making a new junction).
Temperature reading is
offset from actual process
temperature, or the output
switches on or off at the
wrong temperature. The off-
set changes with changes in
process temperature.
• Copper wire was used instead of ther-
mocouple extension wire. Connectors
of metals different than thermocouple
metal were used to splice or make con-
nections.
• Check thermocouple connections. Check to
make sure that only thermocouple extension
wire of the correct type was used to extend
thermocouple leads. Replace if necessary.