Operating instructions

75D0004 3
MLDV Series Gas Fireplace
FP1183
max height
(continued)
This Gas Fireplace has been approved for,
Vertical installations up to 40' (1 m) in height. Up to a 10' (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90° elbows. Figure 30

Figure 31 -
Maximum Elbow Usage
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by
18" (450 mm).
Example: Maximum horizontal length
No elbows = 10’ (3 m)
1 x 45° elbows = 8.5’ (.6 m)
 x 45° elbows = 7’ (.1 m)
A minimum of an 8' (.5 m) vertical rise is required.
Two sets of 45°elbows offsets may be used within the
vertical sections. From 0 to a maximum of 8' (.5 m)
of vent pipe can be used between elbows. Figure 31
Determine the roof pitch and use the appropriate
starter kit for offset installation.
The maximum angular variation allowed in the system
is 70°. Figure 31
The minimum height of the vent above the highest
point of penetration through the roof is ' (610 mm).
Example: Elbow 1 = 90°
Elbow  = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 70°
10'
Maximum
10'
Maximum
40' Max. Height
8' Min. Height
Support Straps
Every 3'
Figure 30 -
Support Straps for Horizontal Runs
40' Max. Height
8' Min. Height
Support Straps
Every 3'
FP1183
1
2
3
4
1
2
3
4
FP1179
max bends