Operating instructions
LCUF Vent Free Firebox
26D4721
7
Carefully select the best location for installation of your
vent-free firebox. The following factors should be taken
into consideration:
• Clearance to side wall, ceiling, woodwork and windows.
Refer to “Clearances/Height Requirements" on Page 8.
Minimum clearances to combustibles
• Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
• Installation must provide adequate ventilation and com-
bustion air.
•
• Location should be out of high traffic or windy or drafty
areas.
•
• Never obstruct the front opening of the vent-free firebox
or restrict the flow of combustion and ventilation air.
• Minimize modifications to existing construction. Refer
to Figure 3 for location suggestions.
• Do not install in the vicinity where gasoline or other
flammable liquids may be stored. The vent-free firebox
must be kept clear and free from these combustible
materials.
Figure 3 -
Possible Locations of Firebox
FP2440
fireplace locations
Ensure that minimum clearances shown in Figures 4
through 7 are maintained. Left and right clearances are
determined when facing the front of the firebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
fire hazard.
1. The clearance from the inside
of the appliance to any combustible wall should not be
less than 6". Figure 4
2. The ceiling must be at least 42”
from the top of the firebox opening. Figure 4
3. The appliance may be placed
against a combustible back wall.
6"
Minimum
42"
Minimum
6"
Minimum
FP2687
minimum clearances
Figure 4 -
Clearance and Height Requirements
FP2687
This inner chamber firebox floor must
be installed at least 1" above any combustible flooring
material, such as carpeting or asphalt tile, which is
closer than 14" to the base of the firebox. Figure 5
Or
The inner chamber firebox floor may be installed nearer
to the floor if a minimum of 14" of noncombustible ma-
terial such as slate or marble is installed between the
base of the firebox and the combustible flooring. Figure
6