Operating instructions
LCUF Vent Free Firebox
10
26D4721
Consult all local codes. All gas piping must be installed to
comply with local codes, or in the absence of local codes,
with the latest edition of the National Fuel Gas Code ANSI
Z223.1/NFPA54.
The 1/2" gas line may enter either from the left side or right
side of the firebox. Gas access holes are provided on both
sides of the firebox.
A listed manual shutoff valve must be installed upstream
of the appliance. A union tee and plugged 1/8" NPT pres-
sure tapping point should be installed upstream of hte
appliance.
A sediment trap may be upstream of the heater to prevent
moisture and contaminants from passing through trap to
the heater controls and burners. Failure to do so could
prevent the heater from operating reliably. Consult appli-
cable codes.
An external regulator must be used on all propane/L.P.G.
heaters, in addition to the regulator fitted to the heater, to
reduce the supply tank pressure to 13" w.c. (maximum).
Any copper tubing used to supply propane / L.P.G. from
the tank must be internally tinned.
After completing connection, test all gas joints from the
gas meter to the gas heater regulator for leaks. Using
soap and water solution or a gas sniffer. DO NOT USE
AN OPEN FLAME.