Operating instructions

33D4051 17
9"
Minimum
42"
Minimum
9"
Minimum
12"
2 1/2"
10"
19"
CLEARANCES and HEIGHT REQUIREMENTS
Figure 20 - Minimum Mantel Clearances
Canopy
Ensure that minimum clearances shown in Figures 14 and 15 aremaintained.Leftandrightclearancesaredeterminedwhen
facingthefrontoftherebox.
Follow these instructions carefully to ensure safe installation. Failure to follow these requirements may create a re
hazard.
1. Sidewall Clearances — The clearance from the inside of the appliance to any combustible adjacent wall should not
be less than 9" for the 24DBXC/24VFSC and 32VFSC. See Figure 19.
2. Ceiling Clearance —Theceilingmustbeatleast42"fromthetopofthereboxopening.See Figures 19 and 20.
3. Back Wall Clearance —Theappliancemaybeplacedagainstacombustiblebackwall.
4. Floor Clearance —Thereplacemaynotbeinstalledontoanycombustibleooringmaterial,suchascarpeting,vinyl
or tile without the hearth or a min. 22 Ga (0.030") metal or a minimum
1
/2"woodenbasecoveringtheentirewidthand
depth of the base. Combustible material must be installed at least 1" away from the front face of the unit.
5. Mantel clearances The canopy supplied with the unit must be installed. If a combustible mantel is installed. It
must meet the clearance requirements detailed in Figure 20.
Figure 19 - Clearances and Height Requirements for
24VFSC/24DBXC/VFS32
WARNING
The dimensions shown in Figures 19 and 20 are minimum clearances to maintain in
installing this heater. Left and right clearances are determined when facing the front
of the heater.
Follow these instructions carefully to ensure safe installation. Failure to follow
instructions exactly can create a re hazard.