Operating instructions

12
58D6002
Unvented Cast Iron Gas Stoves
FP2447
gas connection
3” Min.
Pipe Coupling
To Heater
Valve
Gas
Supply
Inlet
 Hold heater valve firmly with a wrench to prevent movement when connect-
ing to inlet pipe.
Manual Shutoff Valve
Pipe
Stainless
Flexible
Tube
Figure 10 -
Gas Connection

 to reduce the supply tank pressure to a maximum of 13" w.
c. This is in addition to the internal regulator in the heater valve.
Locations that the
Pressure Tapping
Point May Be
Installed
NOTICE: A qualified gas appliance installer must connect the heater to the gas supply.
Consult all local codes.
WARNING
Use new black iron or steel pipe. Internally tinned copper or copper
tubing can be used per National Fuel Code, section 2.6.3, providing gas
meets hydrogen sulfide limits, and where permitted by local codes. Gas
piping system must be sized to provide minimum inlet pressure (Listed
on Data Plate) at the maximum flow rate (BTU/hr). Undue pressure loss
will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance.
Union tee and plugged 1/8" NPT pressure tapping point should be
installed upstream of the appliance. Figure 10
A sediment trap should be installed upstream to prevent moisture and
contaminants from passing through the pipe to appliance controls and
burners. Failure to do so could prevent the appliance from operating
reliable. Figure 11

FP2447
CAUTION
      



