Operating instructions

CDV7 Series Gas Fireplace
69D2027
9

CLEARANCES TO COMBUSTIBLES

Follow these instructions carefully to ensure safe installation. Failure to follow
instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material
other than wood flooring. If installed on carpet or vinyl flooring, the appliance
shall be installed on a metal, wood or noncombustible material panel extending
full width and depth of the appliance.
12"
(305 mm)
Maximum
Depth
72"
(1829 mm)
Minimum
6”
(152 mm)
Minimum
13”
(330 mm)
Minimum
fP2032
wall clearances
Figure 4 -
Ceiling and Side Wall Clearances
FP2032
Ceiling
Side
Wall
Combustible Mantel
FP2285 36
mantel clearances
12” (305 mm)
256O
(64 mm)
13”
(330 mm)
12”
(305 mm)
Finish Wall
Header
Stud
Standoff
Top of Heat
Exhaust Vent
FP2285


 The combustible area above the facing must not protrude
more than 3/4" (19 mm) from the facing. If it does, it is considered
a mantel and must meet the mantel requirements listed in this
manual.

Never obstruct or modify the air inlet or
outlet grilles (louvers). This may create
a fire hazard.
Figure 5 -
Mantel Clearances

6”
5”
3”
45°
1”
256O
156O
356O
456O
FP2286
Mantel leg clear
Side of Fireplace
Opening
Stud
Wall
FP2286
Combustible
Material Area