Technical data

34
7.2 DIP switch settings
OFF
No Mixing Valve Control Fitted
OFF
No Outside Air Sensor Fitted
OFF
Modulating Room Unit Installed
OFF
Analogue Unit 0-3V
OFF
Cascade not fitted
ON
Cascade controls fitted
OFF
* Room unit as Remote Control ONLY
ON
PWM Unit (RE2132)
ON
* Room unit with Sensor
OFF
No External
controls
ON
On/off
Room Stat
Time Clock
Voltfree Switch
OFF
Analogue
cascade
0.15 - 2.85V **
0-3 or
(0-10 via adaptor)
ON
PWM
cascade
(KKM2)
ON
No external controls fitted.
On/Off controls fitted.
Cascade controls for multiple boilers.
ON
Outside Air Sensor Fitted
OFF
Radiator Circuit (mt 70/50ºC)
OFF
1 x Room Unit (RE2132)
ON
2 x Room Units (RE2132)
Off Off Remote / Remote
On Off Sensor / Remote *
On On Sensor / Sensor
Dip Switches 3 & 4
ON
Radiator Circuit (ht 85/65ºC)
ON
Underfloor Zone Mixing Valve Control Fitted (MR03)
Dip Switches 6 & 7 (system operating temperature)
Dip Switch 6
Dip Switch 2
Dip Switch 5
Dip Switch 4 Dip Switch 4
Dip Switch 4
Dip Switch 5
Dip Switch 1
Dip Switch 3
Dip Switch 7
6 OFF 7 OFF Low Temp 55ºC
6 OFF 7 ON Med Temp 70ºC
6 ON 7 OFF High Temp 85ºC
6 ON 7 ON High Temp 85ºC
3
4
* Remote = Room unit with temperature
sensor turned off and unit acting
just as a remote controller
** 0-10 volt control panel via adapto
r
Room unit with temperature sensor active
OFF
Pump
ON
Divertor valve
(Method of charging DHW cylinder)
Dip Switch 8
Sensor=