Technical data

23
There are 3 options for room temperature:-
Both circuits, weather variable, without room control influence.
Room control influence with one room controller for the entire building must be electrically
connected direct to the boiler. Weiland Plug 4.
Independent room influence control with 2 room units (one for the radiator circuit connected
directly to the boiler (Weiland plug 4) and a second room unit for the underfloor circuit connected
to the MR 03 unit).
See section 5.7.5 Room Unit RE 2132. DIP switch No 1 on the boiler control panel should be set to
ON. If the respective power consumption of pumps 2 and 3 are more than 120W, auxiliary relays (auxiliary
contactors) must be installed.
5.8.3 alarm contacts for common fault indication
TheMidimat has a volt free contact, which closes in the case of a fault. This fault contact can be applied
with 230V AC and a maximum of 1A, via an adapter (X9) see fig 5.8f. X9 plug & lead assembly available
from RVR Spare Parts Department.
Fig 5.8f
This contact can be used to trigger an audible or an optical alarm signal in the case of a fault.
Temperature Resistance Voltage* V Voltage* V
°C Over S1,S4, S5, S7 Over S6, AF
-30 1247 1,92
-25 1306 1,98
-20 1367 2,03
-15 1430 2,08
-10 1495 2,14
-5 1561 2,19
0 1630 1,88 2,24
5 1700 1,93 2,30
10 1772 1,98 2,35
15 1846 2,03 2,40
20 1922 2,08 2,45
25 2000 2,13 2,50
30 2080 2,18 2,55
35 2161 2,22 2,60
40 2245 2,27
45 2330 2,32
50 2417 2,36
55 2506 2,41
60 2597 2,45
65 2690 2,50
70 2785 2,54
75 2881 2,58
80 2980 2,62
85 3080 2,66
90 3182 2,70
95 3286 2,74
100 3392 2,78
Table 5 - Sensor temperature versus resistance table
* Measured between both contacts in operation (Sensors are at zero potential against earth)
5.8.2 installation and elect connection MR 03
X9 Plug & Lead
(Part No. 96.00025-0048)
Volt Free Contact
21
21
X9
Control Panel