Technical data

28
16.0 hydraulic system
design
OS = Outside air temperature sensor, used where direct-on-boiler weather
compensated flow temperatures are required.
C = Room temperature controls e.g. RE2132 modulating room unit from RVR Ltd.,
or, separated time clock & room thermostat.
S = HWS sensor from RVR Ltd. Gives 24hr HWS operation.
W/T = Alternative to “S” where “W” is a time switch in series with a cylinder
thermostat “T”. Allows for timed HWS.
PR01=Pump regulation module from RVR Ltd. Allows heating pump to be driven
from boiler, providing for auto operation, frost protector running & summer standstill
exercising.
Must be used where RE2132 modulating room unit is installed. Max pump motor
load 2A.
Divertor valve will require SPDT relay if not spring return.
Divertor valve must be so installed as to spring return to heating.
System type 4
Typical Single MICROMAT EC boiler installation serving heating & domestic hot water. Hot water is priority and is
served via a divertor valve and the boiler’s in built circulating pump where index loss through HWS primaries is less
than 1 metre. Heating circuit index loss exceeds 1 metre and is served via a low velocity mixing header and a
separate pump. Heating flow temperature may be fixed/constant or weather variable.
Condensate
Micromat EC
boiler
LSV
IV
DOC
DOC
Expansion Vessel
Safety Valve
CWM
IV
IV
Strainer
Flow to
system circuits
Return from
system circuits
AV
Low velocity mixing header
Max. velocity 0.5m/s
OS
C
PRO 1
DOC
ST
W
Calorifier