Technical data

34
STRATA2
(Prog#) Description of Prog# Range Preffered Setting
Service Values
51 Output test 030
0 Automatic control
1 All outputs off
2 DHW pump/valve on
3 Circulating pump on
52 Input test 0.5 0
0 Return temperature value
1 DHW temperature value
2 Flow temperature value
3 Outside temperature value
4 Room temperature value
5 0-10 V equiv. Temp
53 Plant Type # refer to drawings at rear of manual * 2736
54 Display of PPS communication details 1..12/0255
Actual Values
55 Actual value of module temperature 1..4/0..140
56 Actual value of system flow temperature 0140
57 Actual value of system return temperature 0140
58 Actual value of Buffer temperature 0140
59 Actual value of DHW temperature 0140
60 Attenuated outside air temperature -50..+50
61 Comp outside air temperature / ––
62 Outside air temperature source 00.01/14.16
RVA 47 Dictated Set Points
65 Maximum flow module temperature 1..4/0..140
66 Maximum system flow temperature 8-85
affected by external inputs
69 Display DHW temperature possible when operating 8-85
70 Nominal room temperature set point 0.0/35.0
71 Set point of room temperature 0.0/35.0
72 Display of flow temperature set point 0140
Heat Generation Values
75 Modules available in cascade 00.1/16.3
76 Lead module in cascade 00.1/16.3
77 Hours to run prior to sequence change 0..990
80 Module #1 total operating hours 0.65535
81 Module #2 total operating hours 0.65535
82 Module #3 total operating hours 0.65535
83 Module #4 total operating hours 0.65535
90 Minimum system water temperature (not always displayed) 0..95
91 Maximum output of module #1 0-255 55
92 Maximum output of module #2 0-255 55
93 Maximum output of module #3 0-255 55
94 Maximum output of module #4 0-255 55
Configuration of Plant
95 HKP pump output function 152
1 Pump operates as internal pump
2 Pump operates heating pump only
3 Pump operates as primary loop pump
4 Pump operates as DHW pump
5 Pump operates as H1 pump
97 Operation of RFO sensor 1..2 1
1 Sensor used for return temperature
2 Sensor used for buffer tank temperature
Table 11
7.2 heating engineer parameter setting (contd)
* = Full controls equipment manual