Technical data

33
STRATA2
7.2 heating engineer parameter setting
To enter the Heating Engineer Parameter Program, the door on the RVA 47 must be opened and
the UP and DOWN Prog buttons must be depressed for at least 3 seconds until #51 appears in
the window.
A # between 51 and 173 will appear in a bracket on the left of the display window. These can be paged
through by using the UP and DOWN buttons.
To alter or input the required data in the selected program line # use the + or buttons.
To leave the Heating Engineer Parameter Setting Menu press the AUTO button.
Table 10
7.1 end user parameter settings (contd)
(Prog#) Description of Prog # Range Inputs Preset
Actual Values
18 Actual room temperature
19 Actual outside temperature -50. +50 ºC
(Pressing the + and buttons
simultaneously until the display
stops flashing will reset the
averaged value)
Maintenance
23 Restore factory presets 0/1 0
Press + and together
for 3 seconds
Time Switch Program DHW
29 Every day the same 1-7 Day
Every day different 17Day
30 1st Ontime -24:00 Hr/Min 06:00
31 1st Ontime -24:00 Hr/Min 22:00
32 1st Ontime -24:00 Hr/Min
33 1st Ontime -24:00 Hr/Min
34 1st Ontime -24:00 Hr/Min
35 1st Ontime -24:00 Hr/Min
Service Indications
49 Module error code 1..4/0..255
(Not always displayed)
50 Indication of faults 0255