Technical data
33
STRATA2
7.2 heating engineer parameter setting
● To enter the Heating Engineer Parameter Program, the door on the RVA 47 must be opened and 
the UP and DOWN Prog buttons must be depressed for at least 3 seconds until #51 appears in 
the window.
● A # between 51 and 173 will appear in a bracket on the left of the display window. These can be paged
through by using the UP and DOWN buttons.
● To alter or input the required data in the selected program line # use the + or – buttons.
● To leave the Heating Engineer Parameter Setting Menu press the AUTO button.
Table 10
7.1 end user parameter settings (contd)
(Prog#) Description of Prog # Range Inputs Preset
Actual Values
18 Actual room temperature – –
19 Actual outside temperature -50. +50 ºC – –
(Pressing the + and – buttons 
simultaneously until the display 
stops flashing will reset the 
averaged value)
Maintenance
23 Restore factory presets 0/1 – 0
Press + and – together 
for 3 seconds
Time Switch Program DHW
29 Every day the same 1-7 Day –
Every day different 1…7Day
30 1st Ontime -24:00 Hr/Min 06:00
31 1st Ontime -24:00 Hr/Min 22:00
32 1st Ontime -24:00 Hr/Min –
33 1st Ontime -24:00 Hr/Min –
34 1st Ontime -24:00 Hr/Min –
35 1st Ontime -24:00 Hr/Min –
Service Indications
49 Module error code 1..4/0..255 – –
(Not always displayed)
50 Indication of faults 0…255 – –