Technical data

26
STRATA2
5.9 connecting a condensate pump
If a suitable drain for condensate disposal is located too high to be able to discharge the condense
water from the boiler, a condense pump must be installed within the base of the boiler.
This condensate pump has a built-in safety device. If the pump outlet is blocked, the water level in the
pump reservoir will rise to just below the rim if the level rises any further, the power to the boiler will be
switched off.
At the right hand side, in the area of the boiler base, there is a socket if no condensate pump is used,
there will be a plug with a control link in place. The condensate pump (KHP1) must be wired into this plug
once the link wire has been removed.
condensate receptacle & pump
model No. KHPI
KHPI
Blue - Neutral
Brown 230V Live
out to boiler interlock.
Supply fails if condense
level too high
Black Permanent Live 230V
Remove Link
Strata 2
Condense
Pump Plug
N
I
L
Fig 5.9a
5.8.3 mixing valve controller RVA 46 installation
procedure
Complete the following steps to install the RVA 46:
Remove the blank panel beside the manager.
Unpack the RVA 46 and insert it in the opening of the control panel.
Place the wiring harness with 7-pin connector in the bottom of the RVA 46 and click the other end into
the wiring upstand at the rear of the boiler.
Place the wiring harness with the 6-pin connector in the top of the RVA 46 and click the other end into
the wiring upstand at the rear of the boiler.
Connect the controller power supply from RVA 47 loom.
Connect LPB circuit (pink and mauve) from RVA 47 loom.
The following can now be connected if necessary:
P1 Pump for mixed circuit Brown
M1 Three way mixing valve Brown
AF1 Outside air sensor Black
RE1 Room unit or thermostat Light-blue
VF1 Mixed flow sensor White
Table 6