21.2 Maintenance (contd)
at b) The pressure of the installation must be between 1 and 2 bar: any possible leaks in the system
must be identified; if necessary, have a pipework engineer solve the problem.
at c) Possible leaks or weeping must be resolved immediately.
at d) In case of water leakage or ingress from the air supply pipe, the cause must be found.
at e) The siphon must be rinsed. With the burners removed, use a filling hose to insert water into
the heat exchanger, which will automatically reach the siphon. Rinse volume should be a
minimum of 2 litres.
at f) Draw your conclusions from the service screen and attend to those parts that have caused any
faults.
at g) and at h)
If necessary, adjust the gas setting on the gas valves.
at i) If the in built pumps make an un-natural noise, and in particular if the pumps are more than 5
years old, it is recommended that the pumps should be replaced by way of preventive action.
Note the pumps are fully modulating and do have characteristic yet yet noise which is normal at low
speeds.
at j) NEVER CLEAN THE BURNER ITSELF.
If the interior of the heat exchanger is contaminated and/or there is a deposit on the surfaces
of the coiled stainless steel pipes, the latter must be removed with a hard brush or citric acid.
(DO NOT USE A STEEL BRUSH !) Then remove any dirt with a vacuum cleaner.
at k) If dirt has deposited on the fan blades, each blade must be carefully cleaned, until the blade
material is visible again. If this is not done evenly the fan will not rotate properly and be out of
balance.
at l) Carefully bend the electrode without touching the burner, until the correct distance has been
reached.
IMPORTANT NOTE
IF ANY WATER CARRYING JOINT WITHIN THE BOILER IS DISASSEMBLED THEN THE O RING
SEAL MUST ALWAYS BE REPLACED, LIKEWISE IF ANY OTHER SEAL IS NOTED TO BE DEFORMED
THEN THEY SHOULD ALSO BE REPLACED.
WATER SEALING O RINGS ARE A ONE TIME USE ONLY AND SHOULD NOT
BE RE-USED.
Cancelling the Service Message
Following the maintenance operations, the service message (when
displayed) must be cancelled. This is done by pressing and holding in the
service button for at least 10 seconds.