Technical data

20
STRATA1
Minimum dimensions of flue terminal positions see fig 19
Dimension Terminal Position Balanced flue Non room
room sealed sealed
A Directly below an opening, air
brick, windows etc. Not
Recommended. 300 mm 300 mm
B Below gutters, soil pipes or
drain pipes 75 mm 75 mm
C Below eaves 200 mm 200 mm
D Below balconies or car port
roof. Not Recommended. 200 mm 200 mm
E From a vertical drain pipe or
soil pipe 75 mm 75 mm
F From an internal or external
corner 300 mm 200 mm
G Above ground, intersecting
roof or balcony level 300 mm 300 mm
H From a surface facing the
terminal 2000 mm 2000 mm
I From a terminal facing the
terminal 2000 mm 2000 mm
J From an opening in the car port
(e.g. door, window) into dwelling 1200 mm 1200 mm
K Vertically from a terminal on the
same wall 1500 mm 1500 mm
L Horizontally from a terminal on
the same wall. 300 mm 300 mm
M From the wall on which the
terminal is mounted. N/A 50 mm
N From a vertical structure on the
roof 500 mm N/A
P Above intersection with roof 500 mm 150 mm
15.0 flue terminal positions (contd)
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.
but installation
not recommended.