Technical data

14
STRATA1
Installation of Standard Wall Terminal
In order to determine the length of concentric tube required to correctly terminate a rear outlet
arrangement, the following procedure should be followed.
1. Measure wall thickness W in mm - see fig 10.
2. Mark off and cut flue tubes following guidance shown in fig 11 below.
Flue tubes should be cut to length TL in mm. Both inner and outer tubes should be cut flush with each
other, square and any burrs removed.
Where TL required, is greater than 845 mm, then additional lengths (as appropriate) of 80/125
concentric tube will be required to extend the standard wall terminal.
13.0 room sealed flue installations (contd)
Rear Outlet
170
W
Fig 10.
Plain
Section
Installed
Uppermost
Wall Bezel
Plates
Required Length
Cutting Line
measure from
this point
TL (mm)
TL = W+237mm
Fig 11.
170
c
L
cut flue hole
ΓΈ130
Fig 12.
Detail For Marking
Out For Cutting
Flue Hole For
Rear Flue, Room
Sealed Horizontal
Arrangement