Appliance Error Codes
If a fault is encountered within the appliance or Cascade LPB network, a fault code will
be generated and displayed by the failing module and all LPB networked RVA47 Cascade
Managers.
If a fault is encountered by a module the respective code will be displayed along with a
flashing LED.
Three digit codes will be displayed in two consecutive sections. I.e. 1-53 = 153.
If a fault is encountered by a RVA47 Cascade Manager or communicated to a RVA47
Cascade Manager via the LPB network ER will be generated on the display.
Opening the controllers flap and pressing the Down PROG button twice will gain access
to parameter line 50 where the generated fault code can be reviewed.
In either case the fault code should be noted for future reference.
If the fault is related to a specific module the unit can be rest by pressing the Lockout
Reset Button (9) for at least 3 seconds.
If the fault is related to a RVA47 Cascade Manager or the LPB communication network
the fault code will clear automatically following the rectification of the fault.
This is also applicable following the rectification of any module fault. This can take up to
10 minutes.
Fault Code Description
E-0 No Error Detected
E-10 Outside Air Sensor Fault / Not Detected
E-20 Flow Water Sensor Fault / Not Detected
E-26 System Flow Sensor Faulty / Not Detected
E-28 Flue Gas Sensor Fault / Not Detected
E-40 Return Water Sensor Fault / Not Detected
E-46 System Return Water Sensor Fault / Not Detected
E-50 HWS Sensor Short Circuit 1
E-52 HWS Sensor Short Circuit 2 (Not Used)
E-58 HWS Volt Free Switch Fault / Not Detected
E-60 Faulty Room Sensor
E-61 Faulty Room Sensor
E-62 Incorrect Room Unit Connected
E-77 Air Pressure Sensor Not Detected (Not Used)
E-78 Water Pressure Sensor Defective (Not Used)
E-81 LPB Short Circuit (Boiler Cascade Wiring)
E-82 LPB Address Conflict (Boiler Cascade Settings)
E-86 Short Circuit on PPS Connection (Not Used in Streamline Configuration)
E-91 EEPROM
E-92 Hardware Malfunction
E-100 Conflict Between Time of Day Master Control (Boiler / QAA70 / RVA47)
E-110 Module Water Temperature Overheat
E-111 Module Temperature Too High (Auto Resetting)