- Modern Home Products Corporation Indoor Fireplace User Manual
16
Vermont Castings EWF36A
20005167
1. Manville - CERAFORM 126, K=.27,
1/2 inches thick
2. EH2416, K = .458,
1 inch thick required.
A hearth extension is required to protect a combustible
oor in front of the replace. Refer to Figure 26 for mini-
mum dimensions and mounting detail.
The hearth extension described in Figure 26 must be a
durable noncombustible material with a minimum (total)
Rt value of 1.09; refer to Figure 24 for examples. The
overall height (above a combustible oor), depth and
width must be as indicated, with the extension centered
to the replace opening.
The top of insulation must be covered with a non-com-
bustible decorative covering a piece of .018” mini-
mum sheet metal, to protect hearth extension material.
(Fig. 26)
Secure the hearth extension to the oor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the replace
hearth and hearth extension with a noncombustible
material. (Figs. 25 and 26)
Alternate noncombustible materials may be used
providing the (total) thermal resistance (Rt value) of the
alternate material employed is greater than or equal to
R = 1.09 Thermal resistance (R) or thermal conductivity
(K), may be obtained from manufacturer of the material.
Factors are related by the formula K = 1/R. (Fig. 24)
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may
be used, provided thickness of material is sufciently
greater to maintain an equivalent (total) thermal resis-
tance (Rt).
To determine the thickness required for any mate-
rial:
FP550
BR/BC - SEALING
DETAILS
9/29/97
Wall Covering
2 x 4 Header - Do not
notch at standoffs
Noncombus-
tible Decorative
Facing
Seal all cracks
between replace sur-
round (steel) and wall
materials with noncom-
bustible material.
Cast Front
Noncombustible
Decorative Cover-
ing
Safety Strips - Must be
overlapped 1/2” minimum
FP1202
Sealing gaps.
COMMON MATERIALS AND FACTORS
MATERIAL K*
R
MINIMUM
THICKNESS
EH2416
Common Brick
0.916
5.0
2.18 1.0 in.**
0.10 5.46 in.**
(CFM Corporation)
R Value is for 1/2 inch.
* Units of K = BTU/SQ FT/HR/˚F/IN
** Thickness of Listed Material
FP533ADD
Addendum
6/1/99 djt
8/4/99 changed .2 to .1
one inch to 1/2 inch djt
FP533ADD
Hearth extension material factors.
NEW K of new material (per inch) thickness
required = X of listed
thickness K of listed material (per inch) material
T (new) = 5.0/0.458 x 0.50 in. = (new required
thickness).