- Modern Home Products Corporation Indoor Fireplace User Manual

14
Vermont Castings EWF36A
20005167

Run pipe to rooine. Since chimney system must be
vented to the out-of-doors, you use an approved
MHSC termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.

Use same procedure detailed in locating center point of
the ue system.
Drive a nail up through roof at the center point. This will
determine center point on outside of the roof.

Size of roof hole varies with the type of chimney ter-
mination installed. Refer to installation instructions
provided with MHSC chimney termination to nd correct
size of roof hole.
There must be a 2” (51 mm) air space between out-
ermost portion of chimney sections and any adjacent
combustible surfaces. (Combustible surfaces include
burnable materials such as: ceiling members, joists,
ooring, combustible insulation and roof structures.)


Mark an outline of the roof hole around the center of the
point nail.  Hole dimensions given in the chim-
ney top installation instructions are dimen-
sions; therefore, the hole size must be marked on the
roof accordingly.
Cover the opening of the installed chimney so debris
cannot get into the system.
Cut and frame the hole. It is good practice to use fram-
ing lumber that is the same size as the rafters. Install
the frame securely because the chimney top and ash-
ing anchored to the frame must be able to withstand
heavy winds.

Since you have already preplanned the height of your
termination according to the Ten Foot Rule, continue to
install pipe to the predetermined height.
Check the chimney top installation instructions for
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.

Follow the installation instructions provided with the
chimney termination you have selected.
FP1199
EPA36
AIR SPACES
circulating models
3/20/02 djt

Combustible framing material MUST NOT
penetrate AIR SPACE (shaded areas)
Standoff
2”
(51mm)
Firestop
1” (25mm)
Space to Back
1” (25mm)
Air Space
to Sides
Wall
Shield
0” Clearance
to Floor
Hearth Extension
FP1199
 Minimum clearances to combustibles.
1” (25mm) Air
Space to Sides





Refer to Figure 2, Page 5 for an illustration of a typical
chase installation.
 Treatment of restop spacers and construc-
tion of chase may vary with type of building. These
instructions are not a substitute for local building codes.
You  check your local building codes to determine
specic requirements for your city or state. 
Other building materials may be required in addition to
MHSC Firestop Spacers.

All joints between the nished wall and
the replace surround (steel front) must be sealed with
noncombustible material to prevent cold air leakage into
the room. (Fig. 20)
