Datasheet
Page 2 of 3
Eaton.com/9PX TD153008EN December 2013
9PX 8 and 10 kVA split-phase battery backup times (in minutes) **
Load (Watts)
Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
9000
5
13
22
33
47
8100
6
15
25
38
52
7200
7
17
30
44
61
6300
8
20
35
51
71
5400
9
24
43
62
86
4500
12
30
53
77
105
3600
16
40
68
99
135
2700
23
55
95
148
193
***Runtimes are shown at full load with maximum power factor, are approximate and may vary with
equipment, configuration, battery age, temperature, etc. View interactive runtime graphs at
www.eaton.com/9PX
.
Additional technical specifications
General
Graphical LCD Graphical displays UPS status in a single view
LEDs
4 status-indicating LEDs
Topology
Online
Transfer time
0 ms
Diagnostics
Full system self-test at power up; ABM
®
ROO/RPO
Rear deck emergency stop connectors (for remote on/off
and power off)
Rail kit/tower stand
Included with all units
Electrical input
Nominal voltage (user selectable)
120/208, 120/240, 100/200, 110/220, 115/230, 127/220
Default voltage
120/208
Voltage range (full load)
200-280V
(derating)
100-276V
Frequency
50/60Hz
Frequency range (60 Hz)
40/70Hz
Frequency window range (50Hz) 57.5 - 62.5Hz ±0.1 Hz
Electrical output
Power factor
0.9+
Power ratings 6kVA
120/208,120/240
5520 VA / 4968 W (L-N)
100/200
4680 VA / 4212 W (L-N)
110/220 5160 VA / 4644 W (L-N)
115/230 5340 VA / 4806 W (L-N)
127/220
6000 VA / 5400 W (L-N)
Power ratings 8 kVA
8000 VA / 7200 W (L-N)
Power ratings 10 kVA
120/208,120/240 10000 VA / 9000 W (L-N)
100/200
8000 VA / 7200 W (L-N)
110/220
9000 VA / 8100 W (L-N)
115/230, 127/220
10000 VA / 9000 W (L-N)
Steady state voltage regulation 6 kVA
±2% (L-N)
Steady state voltage regulation 8/10 kVA
±1%
Frequency regulation 8/10 kVA
±5% (adjustable from ±1% to ±10%)
Efficiency, resistive load 6 kVA
92.9%
Efficiency, resistive load 8/10kVA
93%