Specifications
Galaxy 5000 technical specifications
MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page
28
Current and protection characteristics
Power rating Pn (kVA at PF = 0.8)
(rated output apparent power)
20 30 40 60 80 100 120
Active power (kW) 16 24 32 48 64 80 96
Input currents
Currents and measurement conditions
N.B. Currents are measured at:
- full rated load, PF = 0.8
- rated voltage of normal AC source is
400 V
- battery float charging.
For normal AC-source rated voltages of
380 and 415 V, multiply the I1 and Iu
values by 1.05 and 0.96 respectively.
Fig 22. Input currents.
I1: current at normal AC input
Iu: load current
Ibmax: maximum battery current
Max. input current I1 (A) for 5 to 10 minutes
of backup time, battery recharging
29 41 53 78 104 130 155
Load current Iu (A) 29 44 58 87 116 145 174
Max. current supplied by battery Ibmax (A) 60 90 120 180 240 300 360
Battery protection using Schneider Electric circuit breakers is advised
Type (3P) NS100 NS100 NS100 NS160 NS160 NS250 NS250
Trip unit TM63D TM100D TM100D TM160D TM160D TM250D TM250D
Mag. setting (A) 500 800 800 800 800 1250 1250
Battery protection
Thermal position 1 1 1 1 1 1 1
Upstream protection
(1)
using Schneider Electric circuit breakers is advised
Separate normal and bypass AC inputs
Type (3P) Compact NS 125N, H or L
(2)
Compact NS 250N, H or L
(2)
Normal AC input (3P)
Trip unit TMD125D TMD 250D
Type (4P) Compact NS 125N, H or L
(2)
Compact NS 250N, H or L
(2)
Bypass AC input (4P)
Trip unit TMD125D TMD 250D
(1) Protection devices for single-UPS units, supplied with 400 V, 50 to 60 Hz, confirmation required.
Check compliance with local standards and suitability for specific installation conditions, notably:
withstand for short-circuit current at point of installation
protection of static-switch semiconductors with respect to maximum permissible currents
discrimination with UPS output protection devices in case of operation via the bypass.
(2) Depending on the installation short-circuit current.