Specifications
Galaxy 5000 technical specifications
MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page
27
Physical characteristics - environment and standards
Power rating Pn (kVA at PF = 0.8)
(rated output apparent power)
20 30 40 60 80 100 120
Active power (kW) 16 24 32 48 64 80 96
Environment
Colour of cabinets RAL 9023
Degree of protection (as per IEC 60529) IP20 and anti-dust filter are optional
Noise level (dBA) ISO 3476 65
Single UPS
100% load
2400 2700 3150 4350 4900 6150 7350
Single UPS
75% load
2200 2400 2700 3500 4000 4750 5550
Heat losses (kW)
Single UPS
50% load
2000 2200 2300 2700 3400 3700 3950
Fan throughput m
3
/h 105 200
without derating 1000 m Maximum altitude
with derating 0.85 at 1500 m - 0.79 at 2000 m - 0.75 at 2300 m - 0.69 at 3000 - 0.59 at 4000 m
without battery -25°C to +70°C dry heat Storage temperature
range
with battery -10°C to +45°C
inverter Full rated load, PF = 0.8: 0 to 40°C
20°C to 25°C recommended for optimum battery operation
Operating temperature
range
battery tolerable: 0 to 35°C (40°C for 8 hours)
optimum: +15°C to +25°C (service life cut in half for every 10°C increase above 25°C)
Relative humidity 45% to 75% without condensation at ambient temperature
Standards
Construction and safety IEC 62040-1-2 / IEC 60950
Performance and topology IEC 62040-3 / EN 62040-3
Immunity IEC 61000-4-2 / EN 62040-2 level 4 (electrostatic discharges: 15 kV air, 8 kV contact)
IEC 61000-4-3 / EN 62040-3 level 3 (radiated electromagnetic fields: 10 V/m)
IEC 61000-4-4 / EN 62040-2 level 4 (fast transients: 4 kV on mains cables)
IEC 61000-4-5 / EN 62040-2 level 4 (high-energy surges: 2 kV coupling between lines)
IEC 61000-4-6 / EN 62040-2 level 3 (conducted immunity: 10 V rms on mains cables)
IEC 61000-4-8 / EN 55024 level 4 (radiated immunity: 30 A/m)
EMC
emission IEC 62040-2: C3 monitored distribution is standard / C2 class A is optional
Harmonics IEC 61003-2 / IEC 61003-4
Design, manufacturing ISO 14001 / ISO 9001
Certification and marking TÜV / CE / LCIE