Specifications
Galaxy 5000 technical specifications
MGE UPS SYSTEMS SPTC5 500 UK – 09/2005 page
26
Communication
Power rating Pn (kVA at PF = 0.8)
(rated output apparent power)
20 30 40 60 80 100 120
Active power (kW) 16 24 32 48 64 80 96
User-Machine Interface (UMI)
Standard Black and white graphical display
- quarter VGA (120 x 93 mm)
- high resolution (320 x 240 pixels)
Operating LEDs (load protected, minor fault, major fault)
On and Off buttons
Help key
Function keys
Menu key
Mimic panel with status LEDs
Communication
Standard 1 relay card with dry contacts, 2 inputs and 6 outputs, 250 V 2 A
Options A second relay card with dry contacts, 2 inputs and 6 outputs
Communication cards:
- RS232 / U-Talk
- JBus/ModBus RS232 or RS485
- SNMP / Ethernet
- XML-Web (HTTP)
- 2 ports with dry contacts and/or remote shutdown
Software
Standard Soft Tunor (parameter setting by trained and qualified personnel)
Options Enterprise Power Manager v2
Physical characteristics - dimensions and weight
Power rating Pn (kVA at PF = 0.8)
(rated output apparent power)
20 30 40 60 80 100 120
Active power (kW) 16 24 32 48 64 80 96
UPS cabinet with built-in battery
Width 1 110 mm H x W x D (mm) 1900 x 1110 x 850
Without battery 453
5 minutes 738 738 738 888 1050
10 minutes 738 738 888 975
15 minutes 738 888 975
Weight (kg)
(depends on backup
time)
30 minutes 888 975
UPS cabinet without battery
H x W x D (mm) 1900 x 710 x 850 Width 710 mm
Weight (kg) 400 520
Battery and auxiliary cabinets
H x W x D (mm) 1900 x 710 x 850 Width 710 mm
Weight (kg) 135
H x W x D (mm) 1900 x 1000 x 850 Width 1 000 mm
Weight (kg) 150
Combinations of battery cabinets for given backup times
W (mm) 710
985
> 5 min
kg
885 985
W (mm) 710 1000 > 10 min
kg
885 1142 1307
W (mm) 710 1000 2x710 710+1000 2x1000
Width and weight of
cabinets with batteries
depending on the
backup time
> 30 min
kg
882 1307 1764 2439 2742
Bypass enclosure or cubicle for parallel connection
150 kVA enclosure, H x W x D (mm) / kg 1000 x 800 x 303 / 71
Max. number of parallel UPS units 4 4 3 2 1 1 1
360 kVA cubicle, H x W x D (mm) / kg 1900 x 715 x 825 / 190
Max. number of parallel UPS units 4 4 4 4 4 3 3
600 kVA cubicle, H x W x D (mm) / kg 1900 x 1015 x 825 / 280
Max. number of parallel UPS units 4 4 4 4 4 4 4