Specifications

Galaxy 5000 technical specifications
MGE UPS SYSTEMS SPTC5 500 UK 09/2005 page
22
4. Functions
Main standard functions
Double-conversion topology (VFI as per standard EN50091) with built-in static switch and manual bypass.
Detection of phase sequence.
PFC rectifier with sixpack IGBT modules to eliminate harmonic injection upstream.
Rectifier/charger walk-in and current limiting to ensure compatibility with gensets.
Backup times up to four hours.
Battery charger adapts to ambient temperature.
Start on battery power (cold start).
Battery housed in UPS cabinet up to 80 kVA.
Battery protected against excessive discharges by a circuit breaker.
Redundant ventilation for the static switch.
Modular parallel connection.
Sequential start of UPS units (parallel configuration).
Multilingual graphical display.
Animated mimic diagram (LEDs).
Time-stamping of last 25 000 events.
Terminal for EPO (emergency power off).
EMC C3 monitored distribution is standard, C2 class A is available on option.
Available options
Operation in ECO mode.
Transversal communication cards (up to four simultaneously).
Supervision and shutdown software.
Galvanic-isolation transformer.
Connections from the top.
B1000 or Cellwatch for battery monitoring block by block.
Backfeed protection on normal and/or bypass AC inputs (built into the UPS cabinet).
Lightning arrestor (built into the UPS cabinet).
EMC C2 class A.
Synchronisation module.
5. Installation
5.1 Modular UPS cabinets
Compact, modular design with total access through the front
Galaxy 5000 implements the latest technical and mechanical advances in terms of electrical and power-
electronic components. The significantly reduced number of components makes possible:
A particularly compact solution, but that ensures easy access for maintenance
Integration of many functions in a single cabinet (eliminationn of harmonics, lightning arrestor, backfeed
protection and redundant ventilation)
Integration of the battery up to 80 kVA (5 minutes backup time), in lateral compartments. The battery can be
hot swapped (inverter running).
This innovative design makes for easy handling and connections, while maintaining access through the front,
a requirement for fast maintenance.
Small dimensions
UPS cabinet with built-in battery - width 1 110 mm
H x W x D: 1900 x 1110 x 850 mm
Up to:
- 80 kVA, backup time 5 minutes
- 60 kVA, backup time 10 minutes
- 40 kVA, backup time 15 minutes
- 30 kVA, backup time 30 minutes.