Specifications
MGE UPS SYSTEMS - Galaxy 3000 Specification 8 Effective: September, 2006
§ Bypass source outside tolerances
§ Battery temperature
§ Additional indications shall provide maintenance assistance
Display of Operating Curves: The graphical display shall be capable of displaying curves and bar
graphs of the above-mentioned measured values for significant periods.
Time-Stamped Historical Events: This function shall time-stamp and store all important status
changes, anomaliesand faults, and make this information available for automatic or user-requested
consultation.
B. LED Status Indicators: The UPS control panel shall provide three LEDs that signal the following
status conditions:
§ Green LED: Load protected
§ Yellow LED: minor fault
§ Red LED: major fault, load not protected
C. On/Off Switch: The UPS shall provide the ON and OFF buttons to start and stop the inverter. The
switch shall provide a built-in time delay to eliminate the risk of inadvertent operation (additional
confirmation is requested). It is possible to remotely activate the OFF function via an isolated dry
contact to create an emergency power off function resulting in:
§ Inverter shutdown
§ Opening of the automatic bypass
§ Opening of the input, bypass, output devices and battery circuit breaker
§ Opening of the isolated dry contact on the programmable relay card
D. Audible Alarm Reset: The UPS shall provide an audible alarm that can be stopped using the user
interface. If a new alarm is sensed after the original alarm has been silenced, it will reactivate the
audible alarm.
E. Emergency Power Off (EPO): The UPS shall be equipped with a local emergency power off button
and dry contact input that can be used to command UPS shut down remotely. Activation of this
command shall lead to the following actions:
§ inverter shutdown
§ opening of the static bypass switch and the battery circuit breaker
§ opening of input and output devices
§ opening of an isolated dry contact on the programmable relay board
F. DB-9 Connector: One DB-9 connector with serial output will be provided for field diagnostics.
G. Dry Contacts: The UPS shall be provided standard with a programmable input/output relay board.
This board shall have 8 dry contacts, i.e., 6 for input signals and 2 for output signals.Contacts shall be
programmed as:
§ UPS on Line
§ Load on Bypass
§ UPS on Battery
§ UPS Battery Low
§ General alarm
§ Remote UPS on (input)
§ Remote UPS off (input)
The contacts will be normally open and will change state to indicate the operating status. The contacts
will be rated at 2.0 A (250 VDC / 30 VDC).