Specifications

MGE UPS SYSTEMS - Galaxy 3000 Specification 1 Effective: September, 2006
MGE UPS SYSTEMS
GALAXY 3000 10-30 kVA UPS
Data Center Grade Three Phase Uninterruptible Power Supply
Guide Specifications
1.0 GENERAL
1.1 SUMMARY
This specification describes a three-phase, on-line, double conversion, solid state Uninterruptible Power
System, hereafter referred to as the UPS. The UPS shall operate in conjunction with the existing building
electrical system to provide high quality power conditioning, back-up power protection and distribution for
electronic equipment loads. The system shall consist of a solid state inverter, power factor corrected rectifier,
a 100% rated for continuous duty static switch, an internal maintenance bypass switch, battery plant, graphical
status/control panel, and synchronizing circuitry as described herein.
1.2 STANDARDS
The UPS shall meet the requirements of the following standards:
A. UL listed under 1778, standards for uninterruptible power supply equipment
B. UL Canada (cUL)
C. FCC rules and regulations of part 15, subpart j, class A
D. IEC 1000 (801) level 4
E. The UPS shall be designed in accordance with the applicable sections of the documents published by:
» National Fire Protection Association (NFPA)/National Electric Code (NEC)
» National Electrical Manufacturer’s Association (NEMA)
» Occupational Safety & Health Administration (OSHA)
1.3 SUBMITTALS
Submittals shall contain the following documentation:
A. Installation Package: Complete electrical characteristics and connection requirements. Provide detailed
equipment outlines with cabinet dimensions and spacing requirements; location of conduit entry/exit
paths; location of floor/seismic mounting; available battery types/sizes; all cabinet weights; heat rejection
and air flow requirements; single-line diagram; control, and external wiring.
B. Product Data: Provide catalog sheets and technical data sheets to indicate physical data and electrical
performance, electrical characteristics, and connection requirements.
C. Manufacturer’s Installation Instructions: Indicate application conditions and limitations of use stipulated
by Product testing agency. Include instructions for storage, handling, protection, examination,
preparation, installation, and starting of Product. Include equipment installation outline, connection
diagram for external cabling, internal wiring diagram, and written instruction for installation.
1.4 FINAL SUBMITTALS
Upon delivery of the UPS system, the following submittals shall be included:
A. A complete set of installation drawings showing all the information stated in section 1.3.
B. An installation and users manual showing safe and correct operation of all UPS functions.

Summary of content (15 pages)