Metasys Connectivity Technical Manual 629.
Metasys Integrator—Metasys Integrator MGE UPS Systems Application
lntroduction This document explains the Metasys Integrator MGE UPS Systems application. Use this document with the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5), which provide information on installing and commissioning the Metasys Integrator unit. For information pertaining to MGE UPS Systems equipment, see applicable MGE UPS Systems documentation (obtainable from your MGE UPS service representative).
N1 LAN EPS-6000 or EPS-3000/ COMET Device Standard NCU RS-232 or RS-485 Metasys Integrator or EPS-6000 Device 50 ft maximum to Converter RS-232 to RS-485 Converter UNT EPS-6000 or EPS-3000/ COMET Device Multiple Devices per Port N2 Bus MGE1 Note: If you use a UPM enclosure, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0) as shown in the figures in this application note.
Component Requirements To integrate MGE UPS Systems, you need the following: • properly installed MGE UPS Systems with appropriate Communication Interface Option (RS-232 or RS-485) • B&B RS-232 to RS-485 converter (485 TBLED) with power supply (if necessary) • cables and connectors for connecting the converter to MGE UPS Systems • Metasys Integrator unit • N2 Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Network) • portable PC for downloading vendor communication ta
Vendor Component Requirements Integration between the Metasys Integrator unit and MGE UPS Systems has been tested with the equipment listed in Table 1. Changes to this equipment or integration of MGE UPS Systems products not discussed in this document require additional software development and testing by Johnson Controls Systems Products. For information on integrating other products, refer to the Custom Integration section in this document.
Design Considerations When integrating MGE UPS Systems equipment, consider the following: • All MGE UPS Systems equipment must be set up and running properly before attempting to integrate with Metasys or Companion Networks. (The MGE UPS Systems representative is responsible for configuration of MGE UPS Systems equipment.) • Make sure each UPS baud rate is set to 9600. (The MGE UPS Systems representative is responsible for setting the baud rate.
Metasys Integrator—Metasys Integrator MGE UPS Systems Application
Cable Connections Cable Pinouts When connecting to an RS-485 converter, use the following cable pinouts for the Metasys Integrator unit to the converter: Vendor Port A or B on Metasys Integrator RS-232 Port on Converter RS-485 TBLED DB-9 Female DB-25 Male Signal Pin DCD RD TD DTR GND DSR RTS CTS 1 2 3 4 5 6 7 8 RS-232 Pin Signal 8 3 2 20 7 6 4 5 DCD RD TD DTR GND DSR RTS CTS (50 ft maximum) Set converter jumpers to Echo Off and Control RTS.
EPS-6000 Pinouts Use the following pinouts for the EPS-6000: Vendor Port A or B on Metasys Integrator RAUZ-XM097 DB-9 Female DB-25 Female Signal Pin FG RD TD GND 1 2 3 5 RS-232 Pin Signal 1 2 3 7 FG RD TD GND (50 ft maximum) MGE3 Figure 6: Metasys Integrator Unit to EPS-6000 Using RS-232 RS-232 to RS-485 Converter Signal TD (A) TD (B) RD (A) RD (B) RS-485 RAUZ-XR11 Terminal Signal 4 or 8 2 or 6 L+ L- Note: Contact MGE UPS for EOL requirements.
Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the other end to the RS-232 port on the MGE UPS Systems equipment or connect the other end to the RS-232 to RS-485 converter.
Metasys Integrator—Metasys Integrator MGE UPS Systems Application
Metasys Integrator Setup To set up the Metasys Integrator unit, use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator setup involves: • downloading the correct vendor communication table (.VCT file) • setting up the ports • setting up the network addressing It is necessary to download a .VCT file only once, even if more than one device is referencing the file. The following table provides information specific to the MGE UPS Systems applications.
Metasys Integrator—Metasys Integrator MGE UPS Systems Application
Point Mapping Tables Unitary, Parallel, and Static Switch Devices To get the hardware reference for mapping points to a CS object (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Current Phase 3 Mains 1 point is AI3. Table 3 shows the points available for mapping in the Unitary, Parallel, and Static Switch devices.
Continued on next page . . .
NPT1 (Cont.
NPT1 (Cont.
Comet UPS Points To get the hardware reference for mapping points to a CS object (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Current Phase 3 Mains 2 point is AI6.
NPT1 (Cont.
Metasys Integrator—Metasys Integrator MGE UPS Systems Application 21
Metasys Network Setup Metasys Network setup is described in the Metasys Integrator technical bulletins. This section contains details specific to MGE UPS Systems applications. Mapping to a CS Object Table 5: Software Model and CS Object Definition Application Software Model Display Attribute (on Tables and Models CD-ROM) (recommended) NT Command Attribute Unitary MGEUPS_U.DDL AI1 (recommended) AI1 Parallel MGEUPS_P.DDL AI1 AI1 Static Switch MGEUPS_S.DDL AI1 AI1 Comet MGECOMET.
Metasys Integrator—Metasys Integrator MGE UPS Systems Application 23
Custom Integration For information on integrating products that are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. If this list does not provide the information you require, consider using the System Integration Project Data Sheet to request a custom contract from the System Integration Team.
Notes Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 www.johnsoncontrols.com FAN 629.5 Metasys Connectivity Technical Manual Metasys Integrator Release 9.0 Printed in U.S.A.