User manual

THE UNINTERRUPTIBLE POWER PROVIDER
Network Management Card – User Manual 34003991EN/GA - 8 -
Z EMC: 89/336/EEC and 93/68/EEC.
1.3.3 Configuration
The user can configure the card with one of the following means:
Z Web browser
Z Local serial link (network parameters)
Z BOOTP/DHCP (network parameters)
1.3.4 Administration
Z Up to 50 workstations protected by Network Shutdown Modules - Central or local configuration.
Z Up to 5 browsers connected at the same time (3 in SSL).
Z Minimum recommended browser versions: Internet Explorer 6.x, Mozilla Firefox 1.5, Netscape 6.x
Z E-mail sending configurable according to UPS alarms and transmission of a periodical report.
Z Control of UPS on/off switching via the HTML interface.
Z Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and optimisation of backup
time by shutting down non-priority systems.
Z Automatic data and time adjustment via NTP server.
Z Protection by encrypted password.
Z Protection by secure SSL connection.
Z Saving of logs in the non-volatile memory.
Z Languages available: English / French / Spanish / German / Italian
Z On-line help in English available for each page.
Z Card firmware updated via the network
1.3.5 Network
Z Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet
1.3.5.1 List of ports used
Z BootP, DHCP UDP 68 , 67
Z HTML TCP 80
Z SSL TCP 443
Z NSM connection TCP 5000
Z SMTP 25
Z NTP 123
Z SNMP V1 161
Z TRAP SNMP 162
1.3.6 Environment sensor
Z Temperature measurement from 0 to 70°C with +/- 1°C accuracy
Z Measurement of humidity from 0 to 100% with +/- 6% accuracy
Z Min / max time-stamped function for temperature and humidity
Z Choice of temperature readings in Celsius or Fahrenheit
Z High and low thresholds, hysteresis and offset adjustable via Web interface