Network Management Card – User Manual 34003991EN/GA - 51 -
6 Configuration via RS232
Z Use the cord supplied with the card.
Z Connect the card to a computer equipped with a hyperterminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity,
1 stop bit, and without flow control.
Z Check that UPS power is on.
Z Enter the MGEUPS or mgeups password (non modifiable).
Z The menu is in English only.
-----------------------------------------------------------------------------
MGE UPS SYSTEMS
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Exit
6.1 Choice 1: Restart / Reset
Use this function to restart the card; two choices are possible
1 : Hardware Reset: Equivalent to a restart of the electrical power supply.
2 : Restart application: Restarts only the application part.
6.2 Choice 2: Network Configuration
Use this function to access network settings.