Owner`s manual
Table 1-4: Alarm Connections
J21 terminal block screw position --- 1 2 3 4 5 6 7 8 9 10 11 12
MAJOR ALARM --- X X
MAJOR ALARM --- X X
No Major Alarm --- X X
No Major Alarm --- X X
Minor Alarm --- X X
No Minor Alarm --- X X
Utility Alarm --- X X
No Utility Alarm --- X X
“X” indicates a short circuit between J21 terminal block points.
1.6 Mechanical Specification
Table 1-5: S4 Receiver Cabinet Mechanical Dimensions and Weights
MODEL
3.5 kVA 7 kVA 10.5 kVA 14 kVA 17.5 kVA 21 kVA
HEIGHT (in/cm) 15.75 / 40.5 21 / 54 26.25 / 67.5 31.5 / 81 36.75 / 94.5 42 / 107.9
DEPTH (in/cm) 18.5 / 47.5 18.5 / 47.5 18.5 / 47.5 18.5 / 47.5 18.5 / 47.5 18.5 / 47.5
WIDTH (in/cm) 17 / 43.7 17 / 43.7 17 / 43.7 17 / 43.7 17 / 43.7 17 / 43.7
RECEIVER WEIGHT (lb/kg) 67 / 30.4 88 / 39.9 100 / 45.4 111 / 50.3 122 / 55.3 136 / 61.7
RECEIVER + MODULES 114 / 51.7 182 / 82.6 241 / 109.3 299 / 135.6 357 / 161.9 418 / 189.6
WEIGHT (lb/kg)
RECEIVER SHIPPING 78 / 35.8 100 / 45.4 112 / 51.6 123 / 55.8 134 / 60.8 148 / 67.1
WEIGHT (lb/kg)
1.7 Environmental Specifications
1.7.1 Operating Temperature
All models operate to specifications from 0 to +50° C (+32° F. to +122° F).
1.7.2 Shipping Temperature
-40° C to +75° C (-40° F. to +192° F.) for shipping;
Not recommended for storage.
1.7.3 Storage Temperature
-40°C to +60°C (-40°F to +166°F)
1.7.4 Operating Humidity
0 to 90% relative, without condensation.
1.7.5 Operating Altitude
200 feet below to 10,000 feet above sea level
3.5 to 21 kVA N+1 Inverter
Introductionpage 1 — 6