Owner`s manual
Table 1-2: Inverter Module Dimensions
Inverter Module HEIGHT (in/cm) DEPTH (in/cm) WIDTH (in/cm) WEIGHT (lb/kg)
64004-9MSK1 5.18 / 13.3 15.12 / 38.85 15.76 / 40.5 46 / 20.44
Note: Weight: 1 six-mod receiver = 135 lbs. 1 UPS Module = 46 lbs.
Total System Weight, 21 kVA system = 411 lbs.
1.3 Electrical Specifications
Electrical Specifications are subject to revision without notice.
1.3.1 DC Input
Nominal: -48Vdc; Operating Range: -39.5Vdc to -60 Vdc
1.3.2 AC Output (per module)
Voltage: 120Vrms or 240Vrms
Current: 25Arms or 12.5Arms
Frequency: 50Hz or 60Hz
Table 1-3: S4 AC Output Current Ratings
UNIT 3.5 kVA 7 kVA 10.5 kVA 4 kVA 17.5 kVA 21 kVA
AC AMPERES) (AC AMPERES) (AC AMPERES) (AC AMPERES) (AC AMPERES) (AC AMPERES)
VAC
100* 27.3 54.5 81.8 109.1 136.4 163.6
110 27.3 54.5 81.8 109.1 136.4 163.6
115 26.1 52.2 78.3 104.3 130.4 156.5
120 25.0 50.0 75.0 100.0 125.0 150.0
200 15.0 30.0 45.0 60.0 75.0 90.0
220 13.6 27.3 40.9 54.5 68.2 81.8
230 13.0 26.1 39.1 52.2 65.2 78.3
240 12.5 25.0 37.5 50.0 62.5 75.0
* 100VAC version needs to be derated.
1.3.3 Efficiency
85% minimum, 88% typical (on-line mode); 97% typical (off-line mode) at full kVA/Watt load.
NOTE
An external DC circuit breaker or fuse should be used at the DC source.
Owner’s Manual
Introduction page 1 — 3