User manual

ENGLISH
Appendices
6.1 Technical specifications
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
(3) Adjustable to 100 V (10% derating of output power) 120 V / 127 V.
(4) Battery Evolution S EXB 1250/1750: 2 strings, each 4 x 12 V / 9 Ah.
(5) Battery Evolution S EXB 2500/3000: 2 strings, each 6 x 12 V / 9 Ah.
This product is designed for IT power distribution system.
Evolution S
1250
Evolution S
1750
Evolution
2000
Evolution S
2500
Evolution S
3000
Output power 1250VA/1150W 1750VA/1600W 2000VA/1600W 2500VA/2250W 2880VA/2700 W
AC input power
Rated input voltage
Input-voltage range
Input-frequency range
Single phase 120 V
89 V to 151 V
(1)
47 Hz to 70 Hz, 56.5 Hz to 70 Hz (60 Hz system)
(2)
Output on battery power
Voltage
Frequency
120 V (+6/-10%)
(3)
50/60 Hz ±0.1%
Battery (sealed lead acid,
maintenance free)
Standard
Additional modules possible
(up to 4 EXB)
4 x 12 V
7.2 Ah
4 x 12 V – 9 Ah
6 x 12 V
7.2 Ah
6 x 12 V
9 Ah
Evolution S EXB 1250/1750
(4)
No
Evolution EXB S 2500/3000
(5)
Environment
Operating temperature range
Storage temperature range
Relative humidity
Noise level
0 to 40ºC
-20ºC to 50ºC
20 to 90% (without condensation)
< 45 dBA < 50 dBA
6 — 1
86-81710-00 A01 Appendices