User manual

Access to Maintenance and
Personalization Data
ENGLISH
Access to Measurements and Personalization Data
Main-output personalization
Voltage-threshold personalization
(1) Low threshold for transfer to battery is 150 V.
UPS-sensitivity personalization
Function Factory Setting Other available settings
UPS-sensitivity level Normal
High or low
Function Factory Setting Other available settings
High threshold for transfer to battery 151 Volts AC +3% 141 to 153 Volts AC
Low threshold for transfer to battery 89 Volts AC +3% 80 to 94 Volts AC
Fader activation threshold 132 Volts AC +3% 127 to 138 Volts AC
Booster activation threshold 102 Volts AC +3% 92 to 108 Volts AC
Maximum input-voltage range Disabled Enabled (1)
Function Factory Setting Other available settings
Output voltage on battery power 120 Volts AC
100/120/127 Volts AC
Overload alarm threshold 105% 30/50/70%
Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install
the Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal
Solution-Pac software).
4 — 1
86-81710-00 A01