HotSwap MBP module operation
UPS start-up with the HotSwap MBP module
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2. Set switch (53) to Normal position.
3. Start the UPS by pressing the ON/OFF button (24) on the UPS control panel.
The load is supplied by the UPS.
LED (51) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP module test
1. Set switch (53) to Bypass position and check that the load is still supplied.
2. Set switch (53) back to Normal position.
The HotSwap MBP module has a rotary switch (53)
with two positions:
Normal – the load is supplied by the UPS,
Bypass – the load is supplied directly by the AC-power
source.