Table 5-7: Efficiency on ECO Mode (All Kinds of Load) and Batteries Fully Charged.
kVA / kW 25% 50% 75% 100% Output load percentage
5 kVA /
4 kWatts
96
95
97
96
96
96
97
96
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7 kVA /
4.9 kWatts
96
95
97
96
96
96
97
96
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11 kVA /
8 kWatts
96
95
97
96
96
96
97
96
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
5.6 Heat Rejection
Table 5-8: Full Load Heat Rejection in BTUs/hr.
System
Operation Mode
On-line On Battery
5 kVA 1350 1861
7 kVA 1654 2280
11 kVA 3033 3723
5.7 Environmental Characteristics
The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 z
to +25°C range and at 5-95% humidity, non-condensing at altitude up to 3280 ft without de-rating.
The storage temperature: -20 to 40°C. Humidity: 5-95%, non condensing. z
Battery back-up time is adversely affected by high and low temperatures. It is significantly reduced at z
temperatures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery
manufacturers no longer guarantee operation due to the risk of thermal runaway.
Air enters through the front air vent grills and exits through the back. Always keep air vent grills z
unobstructed.