User manual

86-86000-00 B02 - Page 63
5. Appendix
Table 5-3: Battery Recharge Time to Recover 90% of the Rated Back-Up Time After Discharge at Full Load.
Configuration for
2 hours back-up time
Configuration for
4 hours back-up time
Configuration for
8 hours back-up time
EX RT 5 7 hours 15 hours 24 hours
EX RT 7 5 hours 12 hours 20 hours
EX RT 11 7 hours 15 hours 24 hours
Table 5-4: Efficiency On-line (RL Load) and Batteries Fully Charged.
kVA / kW 25% 50% 75% 100% Output load percentage
5 kVA /
4 kWatts
90
89
91
90
91
91
91
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7 kVA /
4.9 kWatts
90
89
91
90
91
91
91
90
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11 kVA /
8 kWatts
90
89
91
90
90
90
90
89
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
Table 5-5: Efficiency On-Line (RCD Load) and Batteries Fully Charged.
kVA / kW 25% 50% 75% 100% Output load percentage
5 kVA /
4 kWatts
90
89
91
91
91
91
92
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7 kVA /
4.9 kWatts
90
89
91
91
91
91
92
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11 kVA /
8 kWatts
90
89
92
91
91
90
91
90
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
Table 5-6: Efficiency on Battery (RCD Load).
kVA / kW 25% 50% 75% 100% Output load percentage
5 kVA /
4 kWatts
87
87
89
88
89
89
88
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7 kVA /
4.9 kWatts
87
87
89
88
89
89
88
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11 kVA /
8 kWatts
89
88
90
90
89
89
87
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts