4. Maintenance
4.3 Re-Connecting the Power Module
This operation can be performed without interrupting the load.
Figure 4-2: Reconnect the Power Module.
OFF ON
17
LOAD LEVEL
4 kW/ 5 kVA
23
15
1. Secure the Input/Output box using the three
screws.
2. Reconnect the cables
40
and
42
to the Power
Module.
3. Switch the battery circuit breaker(s)
14
to the ON
position.
4. Check if Normal AC source circuit breaker
8
is
on the ON position.
5. Check that the LED
17
is ON.
6. Turn the manual bypass switch from the BYPASS
to the NORMAL position.
7. Follow initial start up sequence (See Section 3.1)
in
order to personalize the UPS.
8. Push the ON button
23
for more than 3 seconds.
The green LED
15
is ON, and the connected
equipment is now protected by the UPS.