3. Operation
Table 3-3: ON/OFF Features.
Display Factory setting Options Comments
Cold start Disabled Enabled Start on battery.
Forced reboot Enabled Disabled UPS restarts automatically when
normal AC source is restored.
Automatic restart Enabled Disabled UPS restarts automatically when
normal AC source is restored.
Sleep mode Disabled Enabled Automatic shutdown on battery
if output load level < 10%
Remote Command Enabled Disabled Enables shutdown or restart
orders from software.
Table 3-4: Battery Features.
Display Factory setting Options Comments
Battery test Every week No test/daily/monthly
Pre-Alarm 20% 0 to 100% Low battery signal; 1% increment
Runtime choice UPS reads # and type
of Battery Modules
connected
From 50 to 400 Ah Requires CLA Module if using
options (See Section 1.5.8)
Battery deep discharge
protection
Enabled Disabled If disabled, loss of EATON
warranty.