86-86000-00 B02 - Page 37
2. Setup and Installation
2.7 System Connections
WARNING
This type of connections must be carried out by qualified electrical personnel.
Before carrying out any connections, check that battery circuit breaker
14
is OFF
and that the upstream protection devices (Normal and Bypass AC
sources) are open (OFF/OPEN).
2.7.1 Connections with Common Normal and Bypass AC Sources (Single Mains)
Figure 2-11: Power Module I/O Box Terminal Block Diagram.
L6 L5 L2 L1 L1 L4 L3
Jumper
(see note)
Output
200/208/220/230/240 Vac
Normal AC source
200/208/220/230/240 Vac
Bypass AC source
200/208/220/230/240 Vac
Terminal block capacity:
- Max. 4AWG (EX RT 11 )
- Max. 6AWG (EX RT 5/7)
NOTE
The Power Module is factory configured for single input, whereas both Normal z
AC and Bypass AC sources are identical, by means of jumper between L1 and L3.
Jumper must be removed for separate Normal AC and Bypass AC sources z
(2 Mains) or with Frequency Converter application.
Keep Manual Bypass Switch z
7
at Normal position.