User manual
86-86000-00 B02 - Page 21
1. Introduction
1.5.3 Multiple Battery Module Back-up Time at Full Load
Standard EX RT 5/7/11 systems (one Power Module and one Battery Module), offers a standard back-up time of
5 to 12 minutes at full load.
To increase back-up time, it is possible to connect up to 5 additional Battery Modules to the standard system.
See Section 2.8 for connections between standard system and Battery Module (EX RT EXB 5/7/11)
Figure 1-9: Typical back-up time with multiple EXB’s at full load.
7 kVA:
11 kVA:
7 min
5 min
20 min
14 min
32 min
22 min
+ +
45 min
30 min
57 min
42 min
72 min
53 min
Standard
EX RT 5/7/11 systems
Optional
Configurations
5 kVA:
9 min 25 min 45 min 60 min 84 min 100 min
EX RT 5/7/11 EX RT
EXB 5/7/11
EX RT
EXB 5/7/11
EX RT
EXB 5/7/11
EX RT
EXB 5/7/11
EX RT
EXB 5/7/11
EX RT
EXB 5/7/11
See Appendix for additional Back-up time information.
1.5.4 Battery Extension Cable Kit
(6 ft./1.8 m, Part number 86006)
This extended battery cable kit will be used instead of the standard battery cable when Battery Modules (EXBs)
are distant from each other (located in two different enclosures, for instance).
The battery extension cable kit includes a 6 ft. long, straight connector battery power cable, and a 6 ft. long
battery detection cable.