User manual
86-86000-00 B02 - Page 15
1. Introduction
1.1 System Electrical Characteristics
Table 1-3: UPS Characteristics System Ratings.
UPS Characteristics
MAIN 1 (Normal AC Source) default
Power
Rating
Input
Voltage
(VAC)
Input Current (A)
Input
Breaker
(A)
Output
Voltage
(VAC)
Output
Current
(A)
Inrush
Current
Min Max Online Bypass
5 kVA
208
18 32 21.6 19 40
208
19.25
200A/1 ms7 kVA 25 45 30.3 26.65 50 23.5
11 kVA 38 64 44 42 70 47.5
Table 1-4: Transformer Module Characteristics Ratings.
Transformer Module Characteristics
Input Voltage (VAC) 208/240
Output Voltage (VAC) 120/120 208 240
Max. Output Current (A) 33.3/33.3 52 45
CAUTION
Power Module is factory configured at 208 Vac, 60 Hz input and output.
Without transformer, Input and Output of the UPS must always be the same.
On 11 KVA, 10% de-rating for 200/208 VAC.
Isolated 120/208/240 VAC are available with EX RT Transformer Module.