10.3 Mode
(PATH: MENU/PID Setup/Mode
This menu contains the selection of control modes using relays or analog outputs. Press
[ENTER].
This menu assigns a relay or analog output for PID control action as well as details of their
operation. Based on the control device being used, select one of the following three paragraphs
for use with solenoid valve, pulse input metering pump or analog control.
Pulse Length – If using a solenoid valve, select "Relays" and "PL", Pulse Length. Choose the
first relay position as #1 if the Reverse control action is needed. Choose the second relay
position as #2 for Direct acting control. Set the pulse length (feed cycle time) in seconds. A
short pulse length will provide more uniform feed. A longer pulse length will reduce wear on the
solenoid valve. A value of 30 seconds may be a good starting point. The % "on" time in the
cycle is proportional to the control output.
Pulse Frequency – If using a pulse input metering pump, select "Relays" and "PF", Pulse
Frequency. Choose the first relay position as #3 if Reverse control action is needed. Choose the
second relay position as #4 for Direct acting control action. Set the pulse frequency to the
maximum frequency allowed for the particular pump being used, typically 60 to100 pulses/
minute. Control action will produce this frequency at 100% output.
CAUTION: Setting the Pulse Frequency too high may cause the pump to overheat.
Analog – If using Analog control, change "Relays" to "Analogout" using up/down arrow keys.
Choose the first Analogout position as #1 if Reverse control action is needed. Choose the
second Analogout position as #2 for Direct control action. Select the analog output current range
required by the control device, 4-20 or 0-20 mA. Press [ENTER].