Specifications

Transmitter M300 FLOW 66
© 09 / 08 Mettler-Toledo AG, CH-8606 Greifensee, Switzerland Transmitter M300 FLOW
Printed in Switzerland 52 121 319
17 Default Tables
parameter sub parameter value unit
Language English
Passwords administrator 00000
operator 00000
All Relays
(unless otherwise specified)
delay 10 sec
hysteresis 5 %
state normal
hold mode NA
Lockout (on/off) no = off
Channel A (single channel) a flow gpm
Channel A (single channel) c total flow gallons
Channel A (single channel) b (none)
Channel A (single channel) d (none)
Channel A (four channel) flow gpm
Channel B (four channel) flow gpm
Channel C (four channel) flow gpm
Channel D (four channel) flow gpm
Channel a (four channel) total flow gallons
Channel b (four channel) total flow gallons
Channel c (four channel) total flow gallons
Channel d (four channel) total flow gallons
cal constants (for all channels) M=1.0, A=0.0
(for type 2 sensors)
Ks = 100, Fs = 0
If F = 0
then this
table is
ignored
(i.e. it is a
type 1
sensor)
(for type 2 sensors) M = 60
Analog Out (single channel) 1 a – flow
2 c – total flow
Analog Out (four channel) 1 Ch A – flow
2 Ch B – flow
3 Ch C – flow
4 Ch D – flow
all analog out mode 4–20 mA
type Normal
alarm off
hold mode last
Flow value 4 mA 0
value 20 mA 100
Total flow value 4 mA 0
value 20 mA 1,000,000
Set point 1 signal a (single channel
A (four channel)
type off
value 1