Specifications
Transmitter M300 FLOW 50
© 09 / 08 Mettler-Toledo AG, CH-8606 Greifensee, Switzerland Transmitter M300 FLOW
Printed in Switzerland 52 121 319
10 PID Setup
(PATH: Menu/PID Setup)
PID Setup
Tune
Parameters
ModePID A/M PID Display
PID control is proportional, integral and derivative control action that can provide smooth
regulation of a process. Before configuring the transmitter, the following process characteristics
must be identified.
Identify the control direction of the process:
Throttling with signal-to-close type valve – direct acting where increasing measurement pro-
duces increasing control output
Pump or throttling with signal-to-open valve – reverse acting where increasing measurement
produces decreasing control output
Identify the control output type based on the control device to be used:
Pulse Frequency – used with pulse input metering pump
Pulse Length – used with solenoid valve
Analog – used with current input devices such as an electric drive unit, analog input metering
pump or current-to-pneumatic (I/P) converter for pneumatic control valve
Default control settings provide linear control which is appropriate for flow. The non-linear
control settings are used in pH/ORP models of this transmitter. Therefore ignore settings of
deadband and corner points in the Tuning Parameter section below.
Controller with Corner Points
–120%
–100%
–80%
–60%
–40%
–20%
0%
20%
40%
60%
80%
100%
120%
0 100 200 300 400 500 600 700
Flowrate (LPM)
Deadband - value
Proportional limit –100% value
Proportional limit +100% value
Output4
Direct corner point (value, %)
Set point value
Deadband + value
Reverse corner point (value, %)